Hangzhou Li Kang Rubber Technology Co., Ltd.
Main products:LSK Cold Shrink Tube
Products
Contact Us
  • Contact Person : Mr. Xu Aaron
  • Company Name : Hangzhou Li Kang Rubber Technology Co., Ltd.
  • Tel : 86-0571-88682675
  • Fax : 86-0571-88682375
  • Address : Zhejiang,Hangzhou,Xianlin Industrial areas Yuhang District Hangzhou City Zhejiang Province China
  • Country/Region : China
  • Zip : 310000

8.7/15(18)kV Single-core Cold Shrink Joints

8.7/15(18)kV Single-core Cold Shrink Joints
Product Detailed
1,Install easily,excellent characters of elasticity and insulation. 2,The raw materials are imported EPDM Simple installation,requires no special tools.No torches or heat required.Accommodates a wide range of cable sizes.The raw materials are imported EPDM.It has excellent resilience.High effective long life.Use unique expanding technology.We can expand the products with minor diameter. 

Types

Names

Voltage Grade

 Nominal Cross-section of Conductor (mm2)

JLSY-10/1.1

8.7/15kV Single-core Cold Shrink Joints

8.7/15(18)kV

25-50mm2

JLSY-10/1.2

70-150mm2

JLSY-10/1.3

185-400mm2

 

The Main Testing Items For 8.7/15(18)kV Cold Shrink Cable Accessories

No.

Testing Items

Testing Conditions and Standards

Results

Remarks

1

AC withstand voltage test

Neither breakdown nor flashover shall occur at 39kV for 5min

Pass

 

2

Partial discharge test

The magnitude of the discharge at 15kV shall not exceed 10pc

Pass

 

3

Impulses voltage withstand test

Neither breakdown nor flashover shall occur at 10 positive and 10 negative impulses of 95kV

No breakdown no flashover

 

4

Heating cycle (in air)

Temperature stability 2h, cooling 3 h,3 cycles in air at the conductor temperature of 95°C to 100 °C and 23kV

No breakdown. Evaluation by the following test results

 

5

Partial discharge(at the normal operation the conductor's high temperature add 5-10 °C)

The magnitude of the discharge at 15kV shall not exceed 10pc

Pass

 

6

Heating cycle voltage test

Temperature stability 2h, cooling 3h ,60 cycles at the conductor temperature of 95°C to 100 °C and 23kV(30 times in air and 30 times in water)

No breakdown. Evaluation by the following test results

 

7

Partial discharge(at the normal operation

The magnitude of the discharge at 15kV shall not exceed 10pc

Pass

 

8

Thermal short-circuit test

No visible deterioration at 23.0kA,2 short circuit

Pass

 

9

Dynamic short-circuit test

No visible deterioration at 81kA,1 short circuit

Pass

 

10

Impulses voltage withstand

At 10 positive and 10 negative impulses of 95kV

No breakdown no flashover

 

11

AC withstand voltage test

23kV,15min.

No breakdown no flashover

 

12

Humidity tests

11kV,300h

No breakdown no flashover no over-current release

Indoor Termination

13

Salt fog tests

11kV,300h

No breakdown no flashover no over-current release

Outdoor Termination

8.7/15(18)kV Single-core Cold Shrink Joints



Copyright Notice @ 2008-2022 ECVERY Limited and/or its subsidiaries and licensors. All rights reserved.